Electrical Functions

Mechanical Switch
14 (2) DPDT
Rating 4.5 Amps @ 125/250 VAC
16 (2) & 55 (4) V3 SPDT
Rating 10 Amps @ 125/250 VAC, 0.5 Amps @ 125 VDC
17 (2) V3 SPDT Gold Plated Contacts
Rating 1 Amp @ 125 VAC, 0.5 Amps @ 30 VDC
Reed Type Proximity Switch
25 (2) & 58 (4) SPDT Maxx-Guard
Rating – Volts Max. 500 V AC/DC, Current Max. 3 Amps, Power Max. 100 Watts/VA, Min. 3 Watts
40 (2) & 59 (4) SPST Maxx-Guard
Rating 0.15 Amps @ 30 VDC
Inductive Proximity Sensor
33 (2) SST Dual Module Normally Open
Rating 0.3 Amps @ 125 V AC/DC
34 (2) SST Dual Module Normally Closed
Rating 0.3 Amps @ 125 V AC/DC
42 (2) & 52 (4) 2-Wire or 3-Wire V3
E.g. 2-Wire Namur – Current Rating Target On : < 1 mA Target Off : > 3 mA, Nominal Voltage 8 VDC /
3-Wire PNP or NPN – Rating 100 mA @ 60 VDC
43 (2) 2-Wire or 3-Wire Cylindrical or Slotted
E.g. 2-Wire Namur – Current Rating Target On : < 1 mA Target Off : > 3 mA, Nominal Voltage 8 VDC /
3-Wire PNP or NPN – Rating 100 mA @ 60 VDC
44 (2) SST Namur Dual Module
Current Rating Target On : < 1 mA Target Off : > 3 mA, Voltage Range 6 to 29 VDC
Position Transmitter
70 (1) 4 to 20 mA Output Loop Powered (Resistive Type)
Supply Voltage 8 to 28 VDC, Linearity Error <1% of Full Scale
Option – HART Protocol
71 (1) 4 to 20 mA Output Loop Powered (Capacitive Type)
Supply Voltage 12 to 30 VDC
72 (1) Digital Output Bus Powered (Resistive Type) – FOUNDATION Fieldbus / Profibus PA Supply Voltage 9 to 32 VDC
74 (1) 4 to 20 mA Output Loop Powered (High Performance Resistive Type)
Supply Voltage 8 to 28 VDC, Linearity Error <0.5% of Full Scale
Bus Communication
92 DeviceNet Module
2 x Discrete Inputs, Open & Closed / 2 x Power Outputs (Solenoids) 24 VDC, 4 Watts / 1 x 4 to 20 mA Auxiliary Input
93 & 94 FOUNDATION Fieldbus Module
Function 93 (Bus Powered) – 2 x Discrete Inputs, Open & Closed / 2 x Discrete Outputs (Piezo) 2mA @ 6.5 VDC each
Function 94 (Externally Powered) – 2 x Discrete Inputs, Open & Closed / 2 x Power Outputs (Solenoids) 4 Watts Total Combined, Current Limited to 200mA
95 Modbus Module
2 x Discrete Inputs – Open & Closed / 2 x Power Outputs (Solenoids) 10 to 24 VDC / 1 x 4 to 20 mA Auxiliary Input
96 & 97 AS-Interface Module
Function 96 (31 Devices per Network) – 2 x Sensor Inputs – Open & Closed / 2 x Auxiliary Inputs / 2 x Power Outputs (Solenoids) 25 to 30 VDC, 4 Watts
Function 97 w/Extended Addressing (62 Devices per Network) – 2 x Sensor Inputs – Open & Closed / 2 x Auxiliary Inputs / 1 x Power Outputs (Solenoids) 25 to 30 VDC, 4 Watts